The Customer's Situation

Encik Rizal hired a Facebook contractor to install four new Panasonic units in his USJ semi-D. Three units worked fine, but the master bedroom 2.0HP never felt properly cold — hovering at 26-27°C even set to 22°C. The original installer dismissed concerns twice, saying "it's normal." After reading our blog on common installation mistakes, Encik Rizal called us.

Our Diagnosis

Technician Wan found 18°C outlet air (should be 12-13°C for this model). A cracked flare fitting was leaking gas, and the system showed moisture contamination from improper vacuuming. The original installer's shortcuts were the sole cause of the poor performance.

Results

  • Outlet temperature: 18°C → 12°C
  • Room cooling: 45+ min to 26°C → 18 min to 24°C
  • Gas leak permanently fixed
  • Moisture contamination eliminated

Pricing

  • Diagnosis: RM80
  • Flare replacement: RM50
  • Full vacuum + R32 recharge: RM200
  • Insulation sealing: RM50
  • Total: RM380

Issues Identified

  • Brand new 2.0HP inverter only producing 18°C outlet air (should be 12-13°C)
  • Previous installer did not perform proper vacuum — moisture in system
  • One flare connection overtightened and cracked — slow gas leak
  • Copper pipe insulation not sealed at joints
  • Room taking 45+ minutes to reach 26°C

Work Completed

  • Recovered all refrigerant from system
  • Replaced cracked flare fitting
  • Full 20-minute vacuum with professional pump
  • Recharged with correct R32 gas amount per manufacturer spec
  • Sealed all insulation joints
  • Outlet temperature dropped to 12°C, room reached 24°C in 18 minutes
Aircond Not Cold After New Installation by Another Contractor — Fix in USJ Semi-D - completed work

Customer Feedback

"The original installer kept saying the unit was fine. Wan found the problems in 15 minutes — cracked flare and no proper vacuum. After the fix, the bedroom finally feels cold. I wish I had called Total Aircond first instead of going with the cheapest Facebook quote."

— Encik Rizal, USJ