The Customer's Situation
Encik Rizal hired a Facebook contractor to install four new Panasonic units in his USJ semi-D. Three units worked fine, but the master bedroom 2.0HP never felt properly cold — hovering at 26-27°C even set to 22°C. The original installer dismissed concerns twice, saying "it's normal." After reading our blog on common installation mistakes, Encik Rizal called us.
Our Diagnosis
Technician Wan found 18°C outlet air (should be 12-13°C for this model). A cracked flare fitting was leaking gas, and the system showed moisture contamination from improper vacuuming. The original installer's shortcuts were the sole cause of the poor performance.
Results
- Outlet temperature: 18°C → 12°C
- Room cooling: 45+ min to 26°C → 18 min to 24°C
- Gas leak permanently fixed
- Moisture contamination eliminated
Pricing
- Diagnosis: RM80
- Flare replacement: RM50
- Full vacuum + R32 recharge: RM200
- Insulation sealing: RM50
- Total: RM380
Issues Identified
- Brand new 2.0HP inverter only producing 18°C outlet air (should be 12-13°C)
- Previous installer did not perform proper vacuum — moisture in system
- One flare connection overtightened and cracked — slow gas leak
- Copper pipe insulation not sealed at joints
- Room taking 45+ minutes to reach 26°C
Work Completed
- Recovered all refrigerant from system
- Replaced cracked flare fitting
- Full 20-minute vacuum with professional pump
- Recharged with correct R32 gas amount per manufacturer spec
- Sealed all insulation joints
- Outlet temperature dropped to 12°C, room reached 24°C in 18 minutes
Customer Feedback
"The original installer kept saying the unit was fine. Wan found the problems in 15 minutes — cracked flare and no proper vacuum. After the fix, the bedroom finally feels cold. I wish I had called Total Aircond first instead of going with the cheapest Facebook quote."
— Encik Rizal, USJ