Aircond Installation for Commercial Kitchen with Heat and Grease in Kota Damansara

Kota Damansara, Selangor  •  February 2026
Back to Projects
Aircond Installation for Commercial Kitchen with Heat and Grease in Kota Damansara
1.5 days
Job Duration
2
Units Installed
Daikin
Brand
RM6,800
Total Cost

The Customer's Situation

Encik Hafiz runs a popular nasi kandar restaurant in Kota Damansara serving 200-300 customers at lunch. His previous 3.0HP wall-mounted aircond — installed directly above the wok station — died after 14 months with evaporator coils completely sealed by grease. Staff were threatening to quit over 40°C kitchen conditions.

Our Approach

We calculated the total heat load: 3 gas stoves (12,000W) + 2 deep fryers (6,000W) + body heat = ~20,000W. Far beyond what one 3.0HP unit could handle. We installed two 3.0HP Daikin ceiling cassettes away from cooking stations, with washable grease pre-filters and an upgraded exhaust system. The aircond handles the remaining heat after the exhaust removes 40-50% at source.

For guidance, see our article on installing aircond in kitchens and tips on maintaining units between services.

Results

  • Kitchen temperature: 38-40°C → 27-28°C during peak
  • Staff satisfaction dramatically improved
  • Pre-filters catch 70% of grease — staff clean weekly
  • After 6 months of bi-monthly cleaning, both units performing like new

Pricing

  • 2× Daikin 3.0HP cassettes (Blue Fin): RM4,800
  • Installation + ceiling work: RM1,200
  • Exhaust upgrade: RM500
  • Pre-filter sets: RM300
  • Total: RM6,800

Issues Identified

  • 40 sqm kitchen with 3 gas stoves, 2 deep fryers — extreme heat load
  • Previous single 3.0HP wall unit broke after 14 months — coils clogged with grease
  • Kitchen staff working in 38-40°C during lunch rush
  • Undersized exhaust system
  • Wall unit positioned directly above wok station

Work Completed

  • Installed 2× Daikin 3.0HP ceiling cassettes positioned away from cooking stations
  • Added washable mesh grease pre-filters at both intakes
  • Upgraded kitchen exhaust with larger hood covering all stations
  • Used corrosion-resistant Blue Fin coils
  • Set up bi-monthly professional cleaning schedule
  • Kitchen temperature reduced from 38-40°C to 27-28°C during peak hours
Aircond Installation for Commercial Kitchen with Heat and Grease in Kota Damansara - completed work

Customer Feedback

"The previous aircond lasted 14 months. These new ceiling cassettes have been running 6 months and still perform like new thanks to the pre-filters. My cooks are happier and more productive. Best investment for the restaurant this year."

— Encik Hafiz, Nasi Kandar Restaurant, Kota Damansara

Commercial Kitchen Aircond?

Specialised installation for restaurants and commercial kitchens with proper grease management.